There was a power outage happened last Wednesday. It shut down all of the electronics in LASTI.
The model is restarted on m1sus, m1boot, and m1bsc, after rebooting them again after outage. All models are running now except for m1susfcquad.
The Beckhoff was also turned off abruptly. I restarted twinCAT model and tcIOC batch file, but it was not working. The system manager complained about broken modules on SQZ chassis I, right rail. Those modules were indeed not blinking correctly as others. The Ethernet cable and power supplies are running OK. I've restart Beckhoff according to log11802. It took some time for the medm to be refreshed. The broken modules eventually went back up online after me disabling and re-enabling them and restarting. The common mode servo went back online and can lock the cavities.
The power outage also broke the third LV PZT driver chassis. We'll report more details in the next log.